If your ClimateMaster is flashing a code or your thermostat is showing a fault number, this page tells you what it means in plain English. I am a ClimateMaster GeoElite dealer and I maintain 300+ geothermal systems across Oklahoma, so these are codes I read in the field most weeks.
Read this first. A fault code is the system protecting itself. It is a diagnostic, not a repair instruction. Two of these you can usually sort out yourself in ten minutes. The rest need somebody with gauges. I will be straight with you about which is which.
Where the code shows up
Depending on your unit and control board, a ClimateMaster fault shows up one of three ways:
- A number on a communicating thermostat such as the iGate or iGate 2. This is the easiest to read.
- A flash count on the control board LED. You count the flashes between pauses. Three flashes every ten seconds is code 3, and so on.
- A number on the AID Tool or the Virtual AID Tool, which is what I carry.
Write the number down before you do anything else. If the system locks out and you cut power, the code can clear and then I am guessing instead of reading.
ClimateMaster fault code list
This is transcribed from ClimateMaster’s own Service Tool fault list. The codes marked filter or drain are the ones a homeowner can often fix without a service call.
| Code | What it is | Likely causes |
|---|---|---|
| 2 | High Discharge Pressure | filter or drain Dirty air filter in heating. Low airflow in heating. Low water flow in cooling. Low water flow to domestic hot water. Overcharged. Faulty discharge pressure transducer. |
| 3 | Low Suction Pressure | filter or drain Low refrigerant charge. Faulty expansion valve. Incorrect loop configuration. Dirty air filter in cooling. Low airflow in cooling. Low water flow in heating or hot water. Faulty suction pressure transducer. Faulty check valve. |
| 6 | Condensate Overflow | filter or drain Blocked drain. Moisture on sensor. Poor drainage. Clogged air filter. Restricted return airflow. |
| 7 | Over / Under Voltage | Voltage too high. Voltage too low. |
| 10 | ECM Low RPM | Blower not configured properly. Incorrect blower. Blower wiring issue. Blower power issue. |
| 11 | Low Air Coil Pressure | filter or drain Low return air temperature. Clogged air filter. Faulty suction pressure transducer. Insufficient charge. |
| 12 | Control Fault | EXM not properly programmed. Faulty EXM. |
| 13 | Low Pump Flow | Air-locked pump. Pump failure. Faulty flow sensor. Incorrect system setup, single instead of parallel. |
| 14 | High Discharge Temperature | Insufficient charge. Water temp out of range. Air temp out of range. Fouled heat exchanger. Faulty expansion valve. |
| 15 | Discharge Pressure Sensor | Faulty wiring. Faulty transducer. Faulty EXM. |
| 16 | Suction Pressure Sensor | Faulty wiring. Faulty transducer. Faulty EXM. |
| 17 | Space Temperature Sensor | Thermostat wiring issue. Incorrect master/slave setting. Faulty thermostat. Faulty EXM. |
| 18 | Space Humidity Sensor | Thermostat wiring issue. Incorrect master/slave setting. Faulty thermostat. Faulty EXM. |
| 19 | Low Refrigerant Pressure Differential | Stuck reversing valve. Faulty compressor. |
| 20 | ECM Configuration | Incorrect unit configuration. Incorrect motor size. |
| 21 | High Blower Static | filter or drain Clogged air filter. Faulty ductwork. |
| 22 | Grundfos Flow Sensor | Sensor wiring issue. Faulty flow (VFD) sensor. Faulty EXM. |
| 23 | Grundfos Pressure Sensor | Sensor wiring issue. Faulty pressure (DPD) sensor. Faulty EXM. |
| 24 | Leaving Air Temp Sensor | Sensor wiring issue. Faulty thermistor. Faulty EXM. |
| 25 | High EWT Warning | High loop temperature. |
| 26 | Low EWT Warning | Low loop temperature. |
| 27 | Cabinet Temperature Sensor | Sensor wiring issue. Faulty thermistor. Faulty EXM. |
| 28 | No Loop Pump Feedback | No line voltage. Faulty wiring. Faulty EXM. |
| 29 | Low Loop Pump Voltage Warning | Low supply voltage. |
| 30 | Loop Pump Locked Rotor | Contaminants in impeller. Seized impeller. |
| 31 | Loop Pump Voltage Shutdown | Low supply voltage. |
| 32 | Loop Pump Sensor Fault | Faulty RPM sensor. |
| 33 | No DHW Pump Feedback Warning | No line voltage. Faulty wiring. Faulty EXM. |
| 34 | Low DHW Pump Voltage Warning | Low supply voltage. |
| 35 | DHW Pump Locked Rotor | Contaminants in impeller. Seized impeller. |
| 36 | DHW Pump Voltage Shutdown | Low supply voltage. |
| 37 | DHW Pump Sensor Fault | Sensor wiring issue. Faulty thermistor. Faulty EXM. |
| 38 | Suction Temperature Sensor | Sensor wiring issue. Faulty thermistor. Faulty EXM. |
| 39 | Discharge Temperature Sensor | Sensor wiring issue. Faulty thermistor. Faulty EXM. |
| 40 | Entering Hot Water Temperature Sensor | Sensor wiring issue. Faulty thermistor. Faulty EXM. |
| 41 | Leaving Hot Water Temperature Sensor | Sensor wiring issue. Faulty thermistor. Faulty EXM. |
| 42 | Air Coil Liquid Temp Sensor | Sensor wiring issue. Faulty thermistor. Faulty EXM. |
| 43 | Air Coil Vapor Temp Sensor | Sensor wiring issue. Faulty thermistor. Faulty EXM. |
| 44 | Water Coil Vapor Temp Sensor | Sensor wiring issue. Faulty thermistor. Faulty EXM. |
| 45 | Water Coil Liquid Temp Sensor | Sensor wiring issue. Faulty thermistor. Faulty EXM. |
| 46 | Hot Water HX Liquid Temp Sensor | Sensor wiring issue. Faulty thermistor. Faulty EXM. |
| 47 | Spare T1 Temperature Sensor | Sensor wiring issue. Faulty thermistor. Faulty EXM. |
| 48 | Lower Hot Water Tank Temp Sensor | Sensor wiring issue. Faulty thermistor. Faulty WXM. |
| 49 | Upper Hot Water Tank Temp Sensor | Sensor wiring issue. Faulty thermistor. Faulty WXM. |
| 50 | Reduced Hot Water Setpoint Warning | High discharge temperature. High discharge pressure. Fouled heat exchanger. |
| 51 | High Suction Pressure Warning | filter or drain Dirty filter in heating. Low airflow in heating. Low water flow in cooling. Low water flow in water heating. Overcharged. Faulty pressure transducer. |
| 52 | Low Suction Pressure Warning | filter or drain Insufficient charge. Faulty expansion valve. Incorrect loop configuration. Dirty filter in cooling. Low airflow in cooling. Low water flow in heating or hot water. Faulty pressure transducer. Faulty check valve. |
| 53 | Low Discharge Pressure Warning | Low entering water temperature. Low entering air temperature. |
| 54 | Loss of WXM Communications | Faulty wiring from EXM to WXM. Faulty WXM. Faulty EXM. Incorrect master/slave setting. |
| 55 | WXM High Temperature Warning | Elements. Thermostat set too high. |
| 56 | Hot Water HX Performance | Fouled hot water heat exchanger. |
| 57 | Low Discharge Superheat | Faulty expansion valve. Faulty discharge pressure transducer. Faulty or improperly installed discharge temperature sensor. |
| 58 | Low Suction Superheat | Faulty expansion valve. Faulty suction pressure transducer. Faulty or improperly installed suction temperature sensor. |
| 59 | High Suction Superheat | Faulty expansion valve. Faulty suction pressure transducer. Faulty or improperly installed suction temperature sensor. Insufficient charge. Faulty check valve. |
| 60 | General Compressor Fault | Check compressor sub-faults 61 to 71, 75 and 76. |
| 61 | High Temperature Shutdown | Improper contact with heat sink. Damaged inverter thermistor. |
| 62 | High Current at Start Up | Low input voltage. Incorrect compressor wiring. Faulty compressor. Damaged or incorrect inverter board. |
| 63 | High Current Shutdown | Low input voltage. Incorrect compressor wiring. Faulty compressor. Damaged or incorrect inverter board. |
| 64 | High DC Voltage Shutdown | High input voltage. Damaged inverter board. |
| 65 | Current Sensor Warning | Damaged inverter board. |
| 66 | Heat Sink Thermistor Error | Damaged inverter board. |
| 67 | Current Sensor Error | Damaged inverter board. |
| 68 | Lack of Inverter Communication or Initialization | Faulty wiring from MIM to board. Faulty MIM. Damaged inverter board. |
| 69 | Low Voltage Shutdown, Inverter | Low input voltage. Damaged inverter board. Faulty wiring to compressor or between inverter and MIM. |
| 70 | Power Supply Sync Warning | Check input voltage. |
| 71 | Converter Over Current Shutdown | Low input voltage. |
| 72 | Protect Operation, Compressor Current | High load condition. Faulty compressor. Incorrect or damaged inverter board. |
| 73 | Protect Operation, Heat Sink Temp | Improper contact with heat sink. |
| 74 | Protect Operation, Input Current | High load condition. Low input voltage. Water temp at range limit. Air temp at range limit. |
Codes 0, 1, 4, 5, 8 and 9 are listed as no fault or unassigned. Source: ClimateMaster Service Tool Fault Codes. Your model may use a subset of these.
What you can safely check yourself
Three things, and they account for a real share of the geothermal calls I run:
- The air filter. Codes 2, 3, 11, 21, 51 and 52 all list a dirty filter or low airflow as a cause. If your filter is grey, that is your first suspect. Change it, then see if the code comes back.
- The condensate drain, code 6. Blocked drain, poor drainage or moisture on the sensor. Look for standing water in the drain pan or at the unit. If you see water near electrical equipment, stop and call me.
- The thermostat. Check the mode and the setpoint are actually what you meant. A lockout can often be soft reset from the thermostat, which is the safe way to clear it.
Do not do these, and I mean it.
Do not open an energized panel, handle capacitors, bypass a safety, add refrigerant, open a geothermal loop, mix loop chemicals, or reset a breaker over and over. That last one is the common mistake. A breaker that keeps tripping is telling you something, and resetting it repeatedly turns a repair into a replacement. If you smell gas, smell something electrical, see smoke, see arcing, or your carbon monoxide alarm sounds, shut it down, leave, and call 911 or the utility first.
How to clear a ClimateMaster fault code
There are two ways a lockout clears, and the difference matters.
Soft reset. Cycling the thermostat call will clear a lockout on most units. This is the homeowner-safe one. If the code stays gone and the system runs normally, the fault was probably a one-time condition.
Hard reset. Cutting power at the disconnect also clears it. It also wipes the fault memory, which is the information I need. If you have already called me, leave it alone and let me read it.
If the code comes straight back, stop resetting. The lockout is protecting the equipment. A compressor that keeps restarting into a fault condition is a compressor you are going to buy. In 727 geothermal jobs I have replaced 13 compressors, and I would like to keep that number low.
What the common ones usually turn out to be
Code 6, condensate overflow. The most common thing I find on geothermal is drain related. Blocked drain line, algae, a full pan.
Code 13, low pump flow and code 30, loop pump locked rotor. These are loop side. An air-locked pump, a failed pump, or debris in the impeller. This is geothermal specific and it is where a lot of general HVAC companies get lost.
Codes 25 and 26, high or low entering water temperature. Your loop is running hotter or colder than design. That can mean loop length, flow, or a loop that has lost fluid. Worth a real look, not a reset.
Codes 60 through 74. Compressor and inverter faults. Nothing here is a homeowner job. Write the number down and call.
ClimateMaster on geothermal
This is ClimateMaster’s own video, and the homeowner in it is in Edmond, which is inside the area I cover every day.
Video by ClimateMaster. Manufacturer documentation: the ClimateMaster Service Tool fault list and the Tranquility Digital DXM2 troubleshooting guide are both published at files.climatemaster.com.
Common questions
What does a ClimateMaster fault code mean?
It is the control board telling you which protection tripped. Code 6 is condensate overflow, code 2 is high discharge pressure, code 3 is low suction pressure, code 13 is low pump flow. The full list is in the table above.
How do I clear a ClimateMaster fault code?
Cycle the thermostat call for a soft reset. Cutting power at the disconnect is a hard reset and it erases the fault memory, so do not do that if you have already called for service. If the code returns immediately, stop resetting and get it looked at.
Can I keep running my geothermal with a fault code showing?
Sometimes, but it is a gamble. A lockout exists to stop a small problem becoming a compressor. If it is code 6 and you cleared the drain, fine. If it is anything on the loop or compressor side, no.
Why does my ClimateMaster keep locking out on the same code?
Because the condition is still there. A repeating code is a real fault, not a glitch. Write the number down and call 405-375-4822.
Do you work on ClimateMaster units you did not install?
Yes. Most of the ClimateMaster systems I service were installed by somebody else. I am a ClimateMaster GeoElite dealer and IGSHPA accredited.
Got a code you cannot clear?
Tell me the number, your model, and what the system is doing. A geothermal diagnostic is $348 flat, weekday or after hours, with a written report before I leave.